FEATURES
Brings your PROFINET S7 PLC controlled machinery to the web Enables platform neutral and free of charge visualization over all common browsers Lets you monitor and operate your machinery from any mobile anytime, anywhere Comes with touchscreen-ready controls and gadgets for fast implementation without programming
| NSCD-T52-RS/ATVISE/PN | Parameter | Value |
|---|---|---|
| Product | Part number | 1880.110/ATVISE/PN |
| Brief description | Web-HMI Server for S7 PROFINET PLCs | |
| Communication controller | Type | netX 52 |
| Integrated Memory | RAM | 8 MB SDRAM |
| Power supply | Supply voltage | 18 – 30 V DC |
| Current (typically) | 130 mA (at 24 V), 190 mA (at 18 V), 110 mA (at 30 V) | |
| Connector | COMBICON MC 1.5/5, 5-pin | |
| Communication interface 1 | Communication standard | Ethernet |
| Interface type | 10BASE-T/100BASE-TX, isolated | |
| Connector | 2 x RJ45 sockets | |
| Communication interface 2 | Communication standard | Ethernet |
| Interface type | 10BASE-T/100BASE-TX, isolated | |
| Connector | 1 x RJ45 sockets | |
| Auto negotiation | supported | |
| Auto cross over | supported | |
| LED indicators | LEDs | SYSTEM, System status
CONFIG, Configuration status MODBUS Modbus status ACTIVE Visualization status LOAD, File download status ACT, Ethernet activity status LNK, Ethernet link status |
| Permitted ambient conditions | Operating temperature range | 0 °C … +50 °C |
| Humidity | 10 % … 95 % relative humidity (not condensing) | |
| Device | Dimensions (L x W x H) | 88 x 22,5 x 78 mm |
| Weight | appr. 84 g | |
| Protection class | IP20 | |
| Mounting | Top hat rail mounting according to DIN EN 60715 | |
| Conformity | RoHS | Yes |
| Conformance with EMC directives | CE sign | Yes |
| Emission | EN 55011:2009 + A1:2010, Class A | |
| Electrical immunity to interference | EN 61131-2:2008 | |
| Electrostatic discharge (ESD) | According to IEC/EN 61000-4-2:2008: 8 kV Air discharge, Criterion B; 4 kV Contact discharge, Criterion B | |
| Fast transient interferences (Burst) | Zone B, according to IEC/EN 61000-4-4:2012: 2 kV Power supply connector DC, Criterion B; 1 kV Communication lines Ethernet, Criterion B | |
| Surge voltage | Zone B, according to IEC/EN 61000-4-5:2006: 0.5 kV CM/DM Power supply connector DC, Criterion B; 1 kV CM Communication lines Ethernet, Criterion B |
| Communication with S7 | Parameter | Value |
|---|---|---|
| SIMATIC S7 PLC | PLC types | S7-1200/1500, PROFINET S7-300/400 |
| PLC Ethernet protocol | RFC1006, Port 102, on PROFINET |
| Ethernet | Parameter | Value |
|---|---|---|
| Ethernet communication | Transmission rate | 10/100 MBit/s |
| Connections | Min. 3 TCP connections to browser at the same time possible. | |
| Data transport | TCP/IP | |
| Integrated Server/Clients | FTP server | RFC 959, Port 21, passive mode |
| HTTP server | RFC 2616, Port 80, HTTP/1.1 | |
| SNTP client | RFC 2030, Port 123, time synchronization |
| WebServer | Parameter | Value |
|---|---|---|
| Integrated WebServer | Supported protocol | HTTP/1.1 – Hypertext Transfer Protocol (RFC 2616) |
| Maximum number of sockets | Min. 3 browser connections at the same time | |
| Supported HTTP methods | GET, HEAD, POST | |
| atvise webMI standard | Supported | |
| Request URI to file system mapping | Supported | |
| Media type recognition from filename suffix | Supported | |
| Server Side Includes (SSI) | Supported | |
| Chunked Transfer Encoding | Not supported | |
| Version | 1.1.0 |
| Time management | Parameter | Value |
|---|---|---|
| Real-time clock | Type | Hardware supported |
| Precision | 20 ppm | |
| Power failure-safe | Yes | |
| Buffering | Min. 7 days, maintenance-free by SuperCap | |
| Synchronization | Manually or cyclically by SNTP (via 123/UDP port) |
| Visualization | Parameter | Value |
|---|---|---|
| Visualization | Web visualization | atvise webMI with Hilscher plug-ins |
| Engineering tool | atvise builder by Certec | |
| Variables/data points | Limited by memory only: 1 KByte web applikation memory per variable | |
| Web memory consumption | 200 KByte per visualization page (typically) | |
| Standard functions | Alarm, trend and user management | |
| Adaptability | Entirely customizable using Java scripting | |
| Multilingualism | Standard: german/english (can be extended) | |
| Web application memory | 6 MB non-volatile FLASH memory | |
| Trending | Trend variables | Up to 32 Variables possible |
| Sampling rate | 200 ms to 24 hours | |
| Recording time | Depending on the number of variables and the sampling rate. Example: 8 Variables @ 60 sec. sampling rate = 45 days; 18 Variables @ 60 min. sampling rate = 1200 days | |
| Trending memory | 8 MB non-volatile FLASH memory |
| Supported web browser | Browser | Version |
|---|---|---|
| Web browser supported by atvise with min. 3 simultaneously active connections | Microsoft Internet Explorer | 8 (with VML conversion), 9 and 10 |
| Mozilla Firefox | 24 | |
| Apple Safari | 5.1.7 | |
| Google Chrome | 31 | |
| Opera | 16 | |
| Blackberry | 6 or 10 |