Petroleum tank level monitoring with HART radar, Ex ia barriers and PROFIBUS PA
How do you bring 12 petroleum tank levels onto one DCS operator screen when the radar transmitters speak HART and the plant uses PROFIBUS PA?
The poster from Sundar Techno Solutions, Bengaluru, shows one group of four tanks. A Siemens radar transmitter on each tank measures the distance to the liquid surface and calculates the level. In the control cabinet, a FINT T500 HART-to-PROFIBUS PA gateway collects the four readings. The operator sees each tank under its own tag on the Distributed Control System (DCS). For the proposed 12-tank installation, this arrangement is repeated across three independent HART groups.
What does the FINT T500 do, and why use HART?
The FINT T500, manufactured by Fieldbus International AS, Norway, is a DIN-rail-mounted protocol converter. It acts as the HART master when communicating with the radar transmitters and as a PROFIBUS PA slave when communicating with the control system. One T500 supports up to four HART instruments. In the configuration shown, it reads one primary variable from each radar and presents each value with its measurement status.
HART stands for Highway Addressable Remote Transducer. Its value here is that each radar can report its level digitally under its own address. Set the radar’s primary variable to level, and the operator can see, for example, TK-101 at 5.24 m. The accompanying status helps the DCS distinguish a valid reading from one that needs attention. For a retrofit, this lets the plant retain suitable HART radar transmitters while integrating them into its PROFIBUS system.
Why use an MTL or Pepperl+Fuchs barrier?
Petroleum vapour can form an explosive mixture with air. Even a low-voltage instrument circuit can carry enough energy under a fault to create an ignition risk. In an intrinsically safe design, a certified barrier or isolator limits the electrical energy that can reach the hazardous-area circuit. For this application, the selected interface must also pass bidirectional HART communication, so the T500 can send a request and receive the radar’s reply.
The poster illustrates one barrier channel per radar and shows a Pepperl+Fuchs Z787 as an example. A final selection from Eaton MTL or Pepperl+Fuchs depends on the exact Siemens radar order code and Ex certificate, the cable length and electrical characteristics, the voltage available at the radar, and the earthing arrangement. This matters especially with the T500 because FINT states that its four HART connections are electrically interconnected inside the gateway. The complete four-branch arrangement needs verification before selecting the barrier model.
What do “safe area” and “Ex ia” mean?
The safe area in the poster is the control-room location designated as non-hazardous on the plant’s area-classification drawing. It houses the DCS equipment, cabinet power supply and T500. The hazardous area is the classified location where flammable vapour may be present. The zone at the radar’s process connection can differ from the zone around its external electronics. The plant’s classification drawing determines the requirement at each location.
Ex ia is an intrinsic-safety protection level. It means the circuit is assessed for ignition safety during normal operation and with up to two countable faults. A suitably certified Ex ia circuit can serve a Zone 0 gas atmosphere. The full equipment marking, gas group, temperature class and installation conditions must match the application. A barrier mounted in the safe-area cabinet can protect a field circuit extending into the hazardous area.
How are 12 radars addressed across three groups?
Give the four radars connected to each T500 unique HART addresses 1, 2, 3 and 4. Those numbers can be reused on the next T500 because it manages a separate HART network. On the PROFIBUS side, give each gateway its own available station address. The following is an example plant address plan.
HART group HART address 1 HART address 2 HART address 3 HART address 4 Example T500 PA address
T500 No. 1 TK-101 TK-102 TK-103 TK-104 11
T500 No. 2 TK-105 TK-106 TK-107 TK-108 12
T500 No. 3 TK-109 TK-110 TK-111 TK-112 13
This makes the path easy to trace during commissioning. For example, TK-107 is HART address 3 on T500 No. 2. The DCS receives that tank’s level through PA station 12. The three gateways can share one suitably designed PROFIBUS PA segment, provided its power budget, cable layout, termination and available addresses permit it.
What is PROFIBUS PA, and what powers the system?
PROFIBUS PA means PROFIBUS for Process Automation. It communicates at 31.25 kbit/s and supports data and fieldbus power on the same cable pair. Where the DCS uses PROFIBUS DP, a DP/PA link or segment coupler provides the interface to the PA field segment. fint.no
There are three power arrangements to account for in this poster:
– The T500 gateways: A regulated 24 V DC cabinet supply is a suitable nominal source. FINT specifies 18–30 V DC at the gateway supply input. A common supply with individually protected branches, or separate supplies, can be selected according to the plant’s load and redundancy requirements. Three gateways do not automatically require three power supplies.
– The radar transmitters: Compatible loop-powered radars may receive power through the T500’s HART instrument supply arrangement. The design must leave enough voltage at each radar after losses in the barrier and cable, including during start-up. Four transmitters communicating successfully on a bench is only part of that check.
– The PA segment and DCS: The PA pair receives conditioned fieldbus power through the plant’s PA power system or an appropriate segment coupler. The DCS controller and operator workstation use their plant control-system supplies. The purple PA cable and the screened HART field cables in the poster therefore serve different parts of the installation.
What can Sundar Techno Solutions supply?
For a 12-radar enquiry, STS can quote:
– 3 × FINT T500 DIN-rail HART-to-PROFIBUS PA gateways.
– 12 HART-compatible intrinsic-safety barrier channels, with Eaton MTL or Pepperl+Fuchs models selected after loop verification.
– Screened twisted-pair HART instrument cable for the tank runs and PROFIBUS PA Type A cable where required.
– Industrial 24 V DC power supplies, branch protection, DIN rails, terminals, cable glands and earthing accessories.
– PA power conditioners, DP/PA couplers, junction boxes and terminators where the existing DCS infrastructure requires them.
– Industrial panel PCs, operator displays and rackmount computers for control-room visualisation where included in the project scope.
Why STS? A tank-farm enquiry often starts with a converter part number. The practical questions are what voltage reaches the farthest radar, whether the selected barrier passes HART, which DCS tag belongs to each tank, and what PA infrastructure the plant already has. Share the radar order code and Ex certificate, area classification, longest cable run and DCS/PA interface details with STS so the quotation reflects the actual installation.
Pan-India project enquiries welcome, including Bengaluru, Chennai, Hyderabad, Pune, Mumbai, Navi Mumbai, Ahmedabad, Vadodara, Jamnagar, Kochi, Mangaluru, Visakhapatnam, Delhi NCR and Kolkata.
Sundar Techno Solutions | Electronic City Phase 2, Bengaluru, Karnataka
Mobile / WhatsApp: +91 9482081014
Email: sales@sundartechno.com
Website: www.sundartechno.com sundartechno.com
FINT T500 India, HART to PROFIBUS PA converter, petroleum tank radar level monitoring, Siemens HART radar integration, Pepperl+Fuchs HART barrier, Eaton MTL intrinsic safety barrier, Ex ia instrumentation, HART multidrop addressing, PROFIBUS PA cable India, tank farm DCS integration, industrial instrumentation Bengaluru.
Hashtags: #SundarTechnoSolutions #FINTT500 #HART #PROFIBUSPA #RadarLevelMeasurement #TankFarmAutomation #IntrinsicSafety #Exia #ProcessInstrumentation #DCSIntegration #OilAndGasIndia #IndustrialAutomation
The poster from Sundar Techno Solutions, Bengaluru, shows one group of four tanks. A Siemens radar transmitter on each tank measures the distance to the liquid surface and calculates the level. In the control cabinet, a FINT T500 HART-to-PROFIBUS PA gateway collects the four readings. The operator sees each tank under its own tag on the Distributed Control System (DCS). For the proposed 12-tank installation, this arrangement is repeated across three independent HART groups.
What does the FINT T500 do, and why use HART?
The FINT T500, manufactured by Fieldbus International AS, Norway, is a DIN-rail-mounted protocol converter. It acts as the HART master when communicating with the radar transmitters and as a PROFIBUS PA slave when communicating with the control system. One T500 supports up to four HART instruments. In the configuration shown, it reads one primary variable from each radar and presents each value with its measurement status.
HART stands for Highway Addressable Remote Transducer. Its value here is that each radar can report its level digitally under its own address. Set the radar’s primary variable to level, and the operator can see, for example, TK-101 at 5.24 m. The accompanying status helps the DCS distinguish a valid reading from one that needs attention. For a retrofit, this lets the plant retain suitable HART radar transmitters while integrating them into its PROFIBUS system.
Why use an MTL or Pepperl+Fuchs barrier?
Petroleum vapour can form an explosive mixture with air. Even a low-voltage instrument circuit can carry enough energy under a fault to create an ignition risk. In an intrinsically safe design, a certified barrier or isolator limits the electrical energy that can reach the hazardous-area circuit. For this application, the selected interface must also pass bidirectional HART communication, so the T500 can send a request and receive the radar’s reply.
The poster illustrates one barrier channel per radar and shows a Pepperl+Fuchs Z787 as an example. A final selection from Eaton MTL or Pepperl+Fuchs depends on the exact Siemens radar order code and Ex certificate, the cable length and electrical characteristics, the voltage available at the radar, and the earthing arrangement. This matters especially with the T500 because FINT states that its four HART connections are electrically interconnected inside the gateway. The complete four-branch arrangement needs verification before selecting the barrier model.
What do “safe area” and “Ex ia” mean?
The safe area in the poster is the control-room location designated as non-hazardous on the plant’s area-classification drawing. It houses the DCS equipment, cabinet power supply and T500. The hazardous area is the classified location where flammable vapour may be present. The zone at the radar’s process connection can differ from the zone around its external electronics. The plant’s classification drawing determines the requirement at each location.
Ex ia is an intrinsic-safety protection level. It means the circuit is assessed for ignition safety during normal operation and with up to two countable faults. A suitably certified Ex ia circuit can serve a Zone 0 gas atmosphere. The full equipment marking, gas group, temperature class and installation conditions must match the application. A barrier mounted in the safe-area cabinet can protect a field circuit extending into the hazardous area.
How are 12 radars addressed across three groups?
Give the four radars connected to each T500 unique HART addresses 1, 2, 3 and 4. Those numbers can be reused on the next T500 because it manages a separate HART network. On the PROFIBUS side, give each gateway its own available station address. The following is an example plant address plan.
HART group HART address 1 HART address 2 HART address 3 HART address 4 Example T500 PA address
T500 No. 1 TK-101 TK-102 TK-103 TK-104 11
T500 No. 2 TK-105 TK-106 TK-107 TK-108 12
T500 No. 3 TK-109 TK-110 TK-111 TK-112 13
This makes the path easy to trace during commissioning. For example, TK-107 is HART address 3 on T500 No. 2. The DCS receives that tank’s level through PA station 12. The three gateways can share one suitably designed PROFIBUS PA segment, provided its power budget, cable layout, termination and available addresses permit it.
What is PROFIBUS PA, and what powers the system?
PROFIBUS PA means PROFIBUS for Process Automation. It communicates at 31.25 kbit/s and supports data and fieldbus power on the same cable pair. Where the DCS uses PROFIBUS DP, a DP/PA link or segment coupler provides the interface to the PA field segment. fint.no
There are three power arrangements to account for in this poster:
– The T500 gateways: A regulated 24 V DC cabinet supply is a suitable nominal source. FINT specifies 18–30 V DC at the gateway supply input. A common supply with individually protected branches, or separate supplies, can be selected according to the plant’s load and redundancy requirements. Three gateways do not automatically require three power supplies.
– The radar transmitters: Compatible loop-powered radars may receive power through the T500’s HART instrument supply arrangement. The design must leave enough voltage at each radar after losses in the barrier and cable, including during start-up. Four transmitters communicating successfully on a bench is only part of that check.
– The PA segment and DCS: The PA pair receives conditioned fieldbus power through the plant’s PA power system or an appropriate segment coupler. The DCS controller and operator workstation use their plant control-system supplies. The purple PA cable and the screened HART field cables in the poster therefore serve different parts of the installation.
What can Sundar Techno Solutions supply?
For a 12-radar enquiry, STS can quote:
– 3 × FINT T500 DIN-rail HART-to-PROFIBUS PA gateways.
– 12 HART-compatible intrinsic-safety barrier channels, with Eaton MTL or Pepperl+Fuchs models selected after loop verification.
– Screened twisted-pair HART instrument cable for the tank runs and PROFIBUS PA Type A cable where required.
– Industrial 24 V DC power supplies, branch protection, DIN rails, terminals, cable glands and earthing accessories.
– PA power conditioners, DP/PA couplers, junction boxes and terminators where the existing DCS infrastructure requires them.
– Industrial panel PCs, operator displays and rackmount computers for control-room visualisation where included in the project scope.
Why STS? A tank-farm enquiry often starts with a converter part number. The practical questions are what voltage reaches the farthest radar, whether the selected barrier passes HART, which DCS tag belongs to each tank, and what PA infrastructure the plant already has. Share the radar order code and Ex certificate, area classification, longest cable run and DCS/PA interface details with STS so the quotation reflects the actual installation.
Pan-India project enquiries welcome, including Bengaluru, Chennai, Hyderabad, Pune, Mumbai, Navi Mumbai, Ahmedabad, Vadodara, Jamnagar, Kochi, Mangaluru, Visakhapatnam, Delhi NCR and Kolkata.
Sundar Techno Solutions | Electronic City Phase 2, Bengaluru, Karnataka
Mobile / WhatsApp: +91 9482081014
Email: sales@sundartechno.com
Website: www.sundartechno.com sundartechno.com
FINT T500 India, HART to PROFIBUS PA converter, petroleum tank radar level monitoring, Siemens HART radar integration, Pepperl+Fuchs HART barrier, Eaton MTL intrinsic safety barrier, Ex ia instrumentation, HART multidrop addressing, PROFIBUS PA cable India, tank farm DCS integration, industrial instrumentation Bengaluru.
Hashtags: #SundarTechnoSolutions #FINTT500 #HART #PROFIBUSPA #RadarLevelMeasurement #TankFarmAutomation #IntrinsicSafety #Exia #ProcessInstrumentation #DCSIntegration #OilAndGasIndia #IndustrialAutomation

Leave a Reply